Tyco Fire Protection Products showcased its experience in water mist suppression options on the International Water Mist Association (IWMA) Conference in Istanbul. Dr Tim Nichols, Sales Director Water Mist EMEA, gave a presentation entitled ‘Fire Protection of Compact Archive Storage using Water Mist’, the place he discussed how the extinguishant is properly suited to the protection of irreplaceable works and artefacts in highly valuable buildings.
Tim’s lecture focused on a hearth test protocol that was formulated to verify the performance and use of Tyco’s personal water mist resolution, AquaMist, in an historical constructing, house to treasured archive storage. The National Fire Protection Association (NFPA) 750 normal requires that, when using a water mist suppression system, hearth testing is undertaken pertinent to the danger. However, of the revealed fire test protocols listed in NFPA 750, none details the necessities for archives that comprise roller (compact) racking. Many of the racks in the targeted constructing are of the ‘roller’ kind, which restrict the amount of house for building companies, together with these for extinguishing system pipework.
Together with the challenge stakeholders, Tyco devised the protocol to incorporate take a look at rig and format, test type, fire load, knowledge acquisition (for example, sensors and imaging), hardware required (such as pumps, nozzles, pipe, tank, generator), and health and safety procedures (for instance, the hearth brigade). The associated efficiency based fire checks have been then designed to replicate the vary of software parameters associated with archive storage.
While ignition sources on the original site have been identified to be minimal, and the principle fire source confirmed as arson, the multi-level constructing poses numerous challenges that needed to be thought of when formulating the fireplace take a look at protocol to ensure effective protection. Low ceilings and numerous obstructions, corresponding to lighting, ducts and pillars, contribute in direction of the confined setting of the archive storage basement stage. Items are stored in a combination of open racks and compact racks, which provide less than a 150mm hole between themselves and the ceiling, and there may be restricted on-site water storage. Pre-test risk evaluation also highlighted restricted access and exits under and above ground, so it’s important for storage space to be maximised and secure egress provided in case of the event of a fire. In addition, the extremely useful nature of the storage contents meant that the chosen fireplace suppression solution had to make sure minimal harm to these historic objects.
To obtain validation, the checks had to meet varied objectives. These comprised rapid control of the fire inside a prescribed space (in this case, outlined as inside a block of racks); management of temperature; attenuation of radiation; and minimisation of collateral damage via water clean-up. They also needed to keep in mind numerous parameters, together with the required high stress mist system; a 30 minute run time; and an annual measurable achievement goal (AMAO) outlined in accordance with a formulation based mostly on the amount of nozzles activating during testing.
The fire checks, carried out for both open and curler racks with minimum storage gaps, had been undertaken in a customized test rig, designed, built and fitted to replicate the precise specification, racking preparations and storage materials of the positioning. Considered a excessive load, the gas materials have been equivalent to that present in archive storage, including paper, books, micro-film and CD circumstances.
Success was outlined by cross or fail standards and determined by detailed quantitative measurements on system configuration, hydraulic analysis, discharge strain, discharge sequence, hearth unfold, temperature, hearth harm and water consumption. In each exams, Tyco’s AquaMist system operated effectively and was noticed to suppress and management the hearth effectively. The venture group was impressed by the shortage of fireside and smoke injury to the supplies and construction and the product has since been installed within the building in query.
Illegal is a unbelievable alternative to highlight the benefits of water mist as a hearth suppression resolution, as well as show its versatility in a variety of functions,” feedback Dr Tim Nichols. Smuggled Identifying a spot out there and taking the chance to formulate a fireplace check protocol for archive storage enabled us to validate the skilled capabilities of our AquaMist system and facilitate protection of a customer’s highly valuable property.”
For more information, go to www.tfppemea.com